40 MW battery: SSO screening and NESO compliance.

Twelve inverters on a 33 kV collector network, connecting in Great Britain under a Large BEGA. NESO wanted evidence of oscillation stability and fault performance. We delivered both from one PSCAD model, in one package.

No.
03
Client
Confidential developer
Plant
40 MW BESS, 12 inverters, 33 kV
Agreement
Large BEGA, Great Britain
Studies
SSO (Tests 3.2.1 and 3.3), FRT, FFCI
Tools
PSCAD/EMTDC v5, MHI DFScan
Result
Stable in all three modes

Every controller that shapes the oscillation response.

NESO wants the submitted model to include every controller that affects the plant, the power plant controller and its delays included. Pick a part to see where it sits.

40 MW BESS MODEL · PSCAD/EMTDCINVERTER CONTROL · EACH UNITPLLphase-locked loopV / Qvoltage controlPactive powerall three feed the inner current loopPLANT CONTROLLERPPC · setpoints · delayssetpoints12 inverters in 6 pairs33 kV COLLECTORGRIDThévenin · min SCLPoCP · Q · V · fDFSCANMIMO scaninjection

Swipe to see it all

Phase-locked loop

Tracks the grid voltage angle so the current controller has a reference to work from. Its bandwidth sets the lowest interaction mode: too fast can excite SSO on a weak grid, too slow loses sync in a disturbance. We modelled it as it is in the inverter firmware.

  • SRF PLL
  • Filter stages
  • PI regulator
  • Key for SSO

Four fault types, export and import.

The plant is a Type C power park module under EREC G99. Each fault lasts 140 ms with 10% retained voltage at the POI, run at +40 MW export and −40 MW import at maximum leading power factor. The same model and fault module give both the FRT and the FFCI evidence.

3PH

Three-phase

140 ms · 10% retained · ±40 MW

PH-PH

Phase to phase

140 ms · 10% retained · ±40 MW

2PH-E

Two phases to earth

140 ms · 10% retained · ±40 MW

1PH-E

One phase to earth

140 ms · 10% retained · ±40 MW

Phases A · B · C, schematic. Measured at the POI: P, Q, line and phase voltages, and positive-sequence active and reactive current.

The two tests NESO asks for on a Large BEGA.

  1. 01

    Test 3.2.1 · Voltage injection

    A 1% voltage ripple at each frequency from 1 to 100 Hz, up to five at a time to save run time. PoC voltage is compared with and without the plant. A ratio below 1 means the plant damps that frequency.

    No growing oscillations
  2. 02

    Test 3.3 · Impedance scan

    MHI’s DFScan injects 0.5% positive- and negative-sequence signals from 1 to 500 Hz and returns the full dq0 impedance of plant and grid. Their product, the minor-loop gain, is checked with the Nyquist criterion.

    No encirclement of −1

Pick a test to see the result.

Mapped to the NESO IBR oscillation guidance.

For a Large BEGA the guidance requires Tests 3.2.1 and 3.3. Fault performance is evidenced separately against the GB Grid Code.

7/7Requirements met

FRT and FFCI were evidenced against the GB Grid Code with the same model, so the SSO and fault results form one consistent package. The PSCAD archive and FSOUT data make it simple to extend if NESO asks for more.

  1. 01

    NESO-compliant EMT software and model

    PSCAD/EMTDC v5 at a fixed 10 µs step, using the same model submitted to NESO.

    Met
  2. 02

    All controllers, including the PPC

    Inner current loop, V/Q, active power, PLL, and the PPC with its cycle time and delays.

    Met
  3. 03

    Test 3.2.1, 1 to 100 Hz

    1% injections in 1 Hz steps, multi-tone and single tone, in all three modes.

    Met
  4. 04

    Test 3.3, 1 to 500 Hz

    DFScan, NESO’s recommended tool, at 0.5%. Plant and grid dq0 matrices saved in FSOUT.

    Met
  5. 05

    PNI partitioning with no change at the PoC

    Seven sub-projects for run time, with an impedance reconciliation showing zero net change.

    Met
  6. 06

    Export, minimum export and import

    +40 MW, 0 MW and −40 MW, in voltage-control mode at minimum short-circuit level.

    Met
  7. 07

    Nyquist stability shown

    None of the three eigenloci encircle −1 in any mode, including a 0 to 3 Hz check.

    Met

What the client received.

01

PSCAD project archive

The runnable model and project files behind every study.

02

Scenario matrix and assumptions

Every case, mode and condition run, and the assumptions behind them.

03

FRT and FFCI results

Ride-through and reactive-current results for each fault case.

04

Impedance scan data

Plant and grid dq0 datasets in FSOUT, with Bode and Nyquist plots.

05

Compliance report

Results mapped, case by case, to the NESO requirements.

06

Review support and handover

Answers to NESO or DNO queries, and notes so the model can be re-run later.

Connecting an inverter-based plant in Great Britain?

Send us the scheme rating, connection voltage, plant type, deadline and the model you have, and we will scope the work.

Next case study · 04 Network reduction: large RMS models made ready for EMT