A generator EMT model, checked against site measurements.

For a synchronous generation plant we built the full PSCAD model: generator, excitation system, stabiliser and protection. Then we checked it against measurements from the real machines and against the system operator’s EMT model checklist.

No.
02
Client
Confidential generation operator
Plant
Synchronous generators
Scope
EMT model, validation and compliance evidence
Tools
PSCAD/EMTDC, PowerFactory
Standard
System operator EMT model checklist
Result
7 of 7 basic checks met

Every part that shapes the transient response.

The machine data came from the operator’s PowerFactory model. The excitation system, stabiliser and protection had no equivalent there, so we built them in PSCAD from the manufacturer’s data sheets. Pick a part to see where it sits in the model.

SYNCHRONOUS GENERATOR EMT MODEL · PSCAD/EMTDCEXCITATION AND CONTROLV refΣEXCITATIONAVRfieldvoltageterminal voltage feedbackGENERATORsynchronous machineSTABILISERPSSLIMITERSUEL · OELPROTECTIONOver/under-voltage · 2 stagesOver/under-frequency · 2 stagesOver-flux (V/Hz)trips the breakerV, ftripSTEP-UP TRANSFORMERGRIDThévenin sourcePOIPOI MEASUREMENT · FFCIP · Q · V · fPositive-sequence currentsReactive current plot for FFCI

Swipe to see it all

Synchronous machine

Each unit’s electrical and mechanical behaviour: voltages, currents, flux, inertia and damping, with saturation from the magnetising curve. The parameters came from the operator’s PowerFactory model, so the two models agree.

  • Electrical and mechanical
  • Inertia and damping
  • Saturation on
  • Multi-mass ready

Two checks. The second one against the real machines.

  1. 01

    PSCAD against PowerFactory

    With the controls switched off, we applied a 100 ms three-phase fault on the transformer HV side in both tools. Matching responses show the machine model is right before any controls go on top.

    Machine model matches
  2. 02

    PSCAD against site measurements

    With the controls on, we laid terminal voltage, field current, field voltage, P and Q from the model over recordings from the real units at several operating points.

    Model follows the plant

Pick a test to see the response.

All seven basic checks met.

The system operator’s EMT model checklist has seven basic checks. This is how the model meets each one.

7/7Basic checks met

FFCI is shown by the connection-point measurement block. The detailed checks follow once the basic checks are accepted, and the model is set up so a governor can be added later for frequency-response work.

  1. 01

    Recognised EMT software

    Delivered in PSCAD/EMTDC v5, the tool the system operator specifies, ready to open and run.

    Met
  2. 02

    Plant, controls and protection

    Generator, AVR, stabiliser, limiters and protection for every unit, not just the machine.

    Met
  3. 03

    Three-phase EMT model

    All three machines and their step-up transformers, in full three-phase detail.

    Met
  4. 04

    Transformer saturation on

    The step-up transformers are modelled with saturation enabled.

    Met
  5. 05

    Runs at a 10 µs time step

    The time step can be set anywhere from 10 to 50 µs.

    Met
  6. 06

    Initialises on its own

    It starts from the user’s terminal conditions, well inside the required time.

    Met
  7. 07

    Model, guide and report

    A runnable model, a user guide to the control blocks, and a report covering both validation stages.

    Met

Need an EMT model that passes the checklist?

Next case study · 03 40 MW battery: SSO screening and compliance